CONSTRUCTION |
|
CONDUCTOR: |
4 pairs of 23AWG solid bare copper. |
INSULATION: |
Polyolefin (PO); blue & white, orange & white, green & white, brown & white. |
TWIST: |
Left-hand. |
ASSEMBLY: |
Left hand direction. |
RIP CORD: |
Polyester multi-yarn. |
JACKET: |
Low smoke zero halogen (LSZH), yellow (Pantone 116C). |
DIAMETERS |
|
JACKET: |
Diameter: 8.3 ±0.2mm; thickness: 1.10 ±0.01mm. |
INSULATION: |
Blue & white: 1.17 ± 0.02mm
Orange & white: 1.12 ± 0.02mm
Green & white: 1.15 ± 0.02mm
Brown & white: 1.10 ± 0.02mm. |
ELECTRICAL |
|
TEMPERATURE & VOLTAGE RATING: |
60°C @300V. |
SPARK TEST: |
2.5kV DC. |
AC LEAKAGE CURRENT: |
=10mA (1.5kV AC) through overall jacket. |
CONDUCTOR DC RESISTANCE: |
=9.38? /100m. |
RESISTANCE UNBALANCE: |
=5%. |
DIELECTRIC STRENGTH: |
1.5kV AC for 2sec. |
INSULATION RESISTANCE: |
=5000M? /m. |
MUTUAL CAPACITANCE: |
=5.6nF /100m. |
CAPACITANCE UNBALANCE: |
=330pF /100m pair-to-ground. |
CHARACTERISTIC IMPEDANCE: |
100±15? @1~100MHz. |
COUPLING ATTENUATION: |
=55dB @30MHz, =41dB @500MHz. |
REGULATORY PERFORMANCE |
|
ANSI/TIA-568-C.2 (2009): |
Balanced Twisted-Pair Telecommunications Cabling and Components Standards. |
ISO/IEC 11801 (EDITION 2.2): |
Information technology - Generic cabling for customer premises. |
IEC 61156-5 (EDITION 2.0): |
Multicore and symmetrical pair/quad cables for digital communications - Part 5: Symmetrical pair/quad cables with transmission characteristics up to 1000 MHz - Horizontal floor wiring - Sectional specification. |
EN 50288-6-1:2013: |
Multi-element metallic cables used in analogue and digital communication and control - Part 6-1: Sectional specification for unscreened cables characterized up to 250MHz - Horizontal and building backbone cables. |
REGULATORY SAFETY |
|
EN 50173-1:2011: |
Information technology - Generic cabling systems - Part 1: General requirements. |
IEC 60332-1-2: |
Tests on electric and optical fiber cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1kW pre-mixed flame. |
IEC 61034-1 / 61034-2: |
Measurement of smoke density of cables burning under defined conditions. |
IEC 60754-2 |
Test on gases evolved during combustion of materials from cables. |
EU DIRECTIVE 2011/65/EC (ROHS 2). |
|
EU DIRECTIVE 2006/95/EC (LVD). |
|
CE COMPLIANCE DATE: 2010.01.01. |
|
USAGE & ENVIRONMENTAL |
|
CABLE COLD BEND: |
-20°C for 4hr. |
INSULATION TENSILE STRENGTH: |
2400 PSI min. (1.69kg/m.sq). |
NVP |
67%. |
TEMPERATURE RANGE: |
Storage & shipping: -20°C to 60°C; installation: 0°C to 60°C; operation: -20°C to 60°C. |
MINIMUM BENDING RADIUS: |
=4 times of overall diameter. |
MAXIMUM PULLING TENSION: |
=110N. |
|
|
FILLER: |
Polyolefin (PO). |